DtiCorp.com Is Introducing The New Honeywell PP905B1008 Static Pressure Sensor
One-pipe, direct-or reverse-acting pressure sensor used with RP908/RP920 Controllers to provide control of duct static, velocity, or differential pressure in airflow applications. Replacement devices available for Johnson, Powers, Robertshaw,etc.
Online, January 6, 2012 (Newswire.com) - Fort Lauderdale, FL - Popular Honeywell online retailer DtiCorp.com (http://www.DtiCorp.com) is introducing the brand new Honeywell PP905B1008 static pressure sensor. One-pipe, direct-or reverse-acting pressure sensor used with RP908/RP920 Controllers to provide control of duct static, velocity, or differential pressure in airflow applications. Replacement devices available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices.
Features:
- Three-diaphragm design minimizes calibration shift with static pressure changes in velocity pressure applications.
- Not sensitive to normal supply air variations.
- Continuous static, total, velocity, or differential pressure indication available by using differential pressure gage.
Specifications:
- Description: Static Pressure Sensor used with RP920/RP908
- Application Type: Static Pressure
- Pressure Range (psi): 2 in. wc
- Pressure Range (kPa): 0.5 kPa
- Maximum Safe Operating Pressure (psi): 25 psi
- Maximum Safe Operating Pressure (kPa): 172 kPa
- Output Pressure Range (psi): 3 psi to 15 psi
- Output Pressure Range (kPa): 21 kPa to 103 kPa
- Connections: Push-on barb for 1/4 in (6 mm) Diameter tubing
- Temperature Range (F): 40 F to 120 F
- Temperature Range (C): 4 C to 50 C
- Setpoint Range (in. wc): 0 in. wc. to 7 in. wc. (Adjustable)
- Setpoint Range (kPa): 0 kPa to 1.7 kPa (Adjustable)
- Mounting: Duct mount
- Dimensions (in.): 8 in high, 9 in wide, 4 1/8 in deep
- Dimensions (mm): 203 mm high, 228 mm wide, 105 mm deep
- Airflow Usage: 0.021 cfm (9.9 ml/s)
- Action: Can be set for Direct Acting or Reverse Acting
- Mainline Air Pressure (max.) (psi): 25 psi
- Mainline Air Pressure (max.) (kPa): 175 kPa
- Mainline Air Pressure (min.) (kPa): 112 kPa
- Span (Non-Adjustable) (in. wc): 2 in. wc.
- Span (Non-Adjustable) (kPa): 0.5 kPa
- Mainline Air Pressure (min) (psi): 16 psi
- Maximum Safe Static Pressure (in. wc): 28 in. wc
- Maximum Safe Static Pressure (kPa): 7 kPa
- Comments: The setpoint determines the midpoint of the span.
About Us: DtiCorp.Com (http://www.DtiCorp.com) carries more than 35,000 HVAC products, including industrial, commercial and residential parts and equipment from Honeywell, Johnson Contols, Robertshaw, Jandy, Grundfos, Armstrong and more. Our online catalog is easy to navigate and search, and all products have a picture and a description. If a customer has any questions about a product, they can call 800-757-5999 and speak with one of our product experts. Our mission is to offer the best prices anywhere to our customers.
Julian Arhire
Manager DtiCorp.com
Phone: 954.484.2929
Fax: 954.484.5155
Web: http://www.DtiCorp.com
###
Share:
Tags: airflow applications, Controllers, differential pressure, direct acting, DtiCorp.com, duct static, Honeywell, One-pipe, PP905B1008, pressure sensor, reverse-ac